HENTG POWER 400kVA 11kV/0.4kV Three-Phase Oil-Immersed Transformer with ONAN Cooling for Commercial & Industrial Use
Transformador imerso em óleo HENTG POWER 400kVA para a Nigéria. 11kV/0,4kV, compatível com IEC 60076. Tanque corrugado e vedações HNBR evitam vazamentos no calor tropical. Enrolamentos de cobre, grupo vetorial Dyn11 lidam com flutuações da rede. Resfriamento ONAN para capacidade de sobrecarga de 1,2x.
1. Product Brief
The HENTG POWER 400kVA oil-immersed transformer is designed for 11kV primary / 0.4kV secondary distribution in commercial complexes and industrial factory environments.
Rated at 50Hz, ONAN (Oil Natural Air Natural) cooling, this three-phase transformer meets IEC 60076 standards.
It is optimized for Nigeria’s grid conditions and tropical ambient temperatures (up to 45°C), providing reliable step-down power from 11kV medium voltage to 400V three-phase / 230V single-phase end-user supply.
2. Why Choose HENTG POWER?
-
IEC 60076-compliant core & windings – Grain-oriented silicon steel (M5 grade, 0.23mm thickness) reduces no-load loss by consistent magnetic flux density (1.65T).
-
Sealed tank design (corrugated wall) – Expansion corrugated fins absorb oil volume variation from -5°C to +55°C ambient, eliminating conservator-related leakage risks.
-
High overload capacity – ONAN cooling allows 1.2x continuous overload for 6 hours within 45°C ambient without winding hotspot exceeding 105°C (class A insulation, 220°C cellulose paper).
-
Dyn11 vector group – Handles unbalanced loads common in Nigerian commercial clusters (shops, factories with welding equipment).
-
Low noise operation – ≤55 dB(A) at 1m distance, measured per IEC 60076-10.
-
Anti-condensation treatment – HV/LV bushing sealing with NBR rubber (shore A 70±5) and hydrophobic coating on terminals for high-humidity coastal regions (Lagos, Port Harcourt).
3. Detailed Specifications & Technical Features (H2: Technical Parameters)
Core Parameters (IEC 60076-1)
-
Rated power: 400kVA
-
Primary voltage: 11kV ±2×2.5%
-
Secondary voltage: 0.4kV
-
Frequency: 50Hz
-
Vector group: Dyn11
-
Impedance voltage: 4.5% (±5%)
Construction & Materials
-
Core: Step-lap stacked, cold-rolled grain-oriented silicon steel (M5, 0.23mm).
-
LV winding: Copper foil (99.9% purity) – better short-circuit withstand than aluminum.
-
HV winding: Copper wire (F class insulation, 155°C rated).
-
Insulation paper: Thermally upgraded kraft paper (220°C melting point, permittivity 3.5).
-
Tank: 3mm steel plate, hot-dip galvanized (Zn coating ≥ 85μm) for corrosion resistance in Nigeria’s humid/saline environment.
Operating conditions
-
Altitude: ≤ 1000m (customizable for Jos Plateau via derating)
-
Ambient temperature: -5°C to +45°C
-
Humidity: ≤ 95% non-condensing
Leakage prevention engineering (for Nigeria)
-
Corrugated tank with no rubber gasket on main body (only on manhole and bushings).
-
Gaskets: HNBR (Hydrogenated Nitrile) for oil resistance, compression set ≤ 20% after 1000h at 120°C.
-
Bushing sealing torque: factory set at 25Nm ±2Nm, with dual O-ring grooves.
-
Paint system: Epoxy primer (80μm) + polyurethane topcoat (80μm) – passed salt spray test 720h (ASTM B117) with no creepage.
4. Pain Point Solution for Nigeria – Minimizing Oil Leakage Risk
Pain point (Nigeria-specific)
-
Frequent grid surges and voltage fluctuations cause internal arcing and gasket aging.
-
High ambient temperature (up to 45°C) + tropical humidity accelerate rubber seal degradation.
-
Poor road conditions during transport lead to tank weld stress cracks.
-
Local maintenance culture often lacks torque wrenches, leading to over/under-tightened bushing nuts.
Our solutions (parameter-supported)
| Pain factor | HENTG POWER design measure | Evidence / specification |
|---|---|---|
| Thermal expansion stress | Corrugated tank with pre-calculated fin volume | Oil expansion volume: 0.45L per 10°C rise for 400kVA; fin capacity = 18L reserve |
| Gasket hardening | HNBR (Hydrogenated Nitrile Butadiene Rubber) | Compression set ≤ 20% after 1000h @ 120°C; oil swell ≤ 10% in 72h (ASTM D471) |
| Weld cracking | Full-penetration robotic welding + X-ray inspection | 100% of main tank welds tested per ISO 17636; no weld repair allowed without re-X-ray |
| Over-tightening damage | Torque-limiting markings on bushing nuts | Factory marking at 25Nm; ±10% tolerance visible after installation |
| Corrosion under gasket | Zinc-rich primer + silicone sealant at joints | Salt spray resistance 720h (ASTM B117) – no red rust |
| Sand/dust ingress | IP54-rated terminal box (on request) | With optional IP54 enclosure for LV side (standard is IP44) |
Result statement (no fake %)
In internal accelerated aging tests (85°C oil temperature, 90% RH, 500h cycle), the corrugated tank and HNBR gaskets showed zero visible leakage; torque retention remained within 22-28Nm range.
5. FAQ for Nigerian Distributors & EPC Contractors
Q1: Can this transformer handle 33kV primary? We sometimes have 33kV feeders in industrial zones.
A: The standard model is 11kV primary. For 33kV applications, we offer a variant with 33kV bushings and reinforced insulation (36kV rated, BIL 170kV). Please specify voltage at order.
Q2: How do you prevent oil leakage during transport on bad roads from Lagos to Kano?
A: All HENTG POWER transformers are shipped with zero oil (dry). We use nitrogen-filled tank pressure (0.2 bar) to detect weld leaks before shipment. After installation, first oil fill is done on-site – this eliminates transit vibration leakage.
Q3: What is the standard warranty and do you have a local agent in Nigeria?
A: 24-month warranty from commissioning date or 30 months from shipment, whichever earlier. We have a technical partner in Lagos with stock of bushings, gaskets, and DGA test kits. Service response within 48 hours.
Q4: Can we use this transformer for a cold storage facility with frequent on/off cycling?
A: Yes – the Dyn11 vector group and copper winding (low thermal expansion mismatch) tolerate daily load cycles. However we recommend no more than 4 full load cycles per day to avoid cumulative insulation stress. For frequent switching (e.g., 10 cycles/day), we suggest optional load tap changer (OLTC) – consult HENTG POWER engineering.
Q5: What type of transformer oil is pre-filled? Can we use local oil?
A: Factory-filled with inhibited mineral oil (IEC 60296, grade A, breakdown voltage ≥ 60kV/2.5mm). Local oil can be used only if it meets same dielectric strength and pour point (-30°C) – we advise sending sample to our lab for compatibility test.
Q6: What grounding system do you recommend for Nigerian factories (TN-C or TT)?
A: The LV winding (0.4kV side) comes with a removable neutral link. For TN-C systems, we recommend solid neutral grounding. For TT, use the neutral link with surge arrester (MOV 275V) – not included but can be ordered as accessory.
6. Our HENTG POWER – Company & Technical Leadership
HENTG POWER specializes in medium-voltage oil-immersed transformers (50kVA to 10MVA) for emerging markets, with a dedicated engineering team for tropical and high-salinity environments.
Technical certifications
-
IEC 60076-1 to -10 compliant design (Type-tested at KEMA or equivalent independent lab)
-
ISO 9001:2015 production facility
-
Short-circuit withstand test passed: 400kVA model at 11kV, 4.5% impedance, 25 cycles (IEC 60076-5)
Key manufacturing capabilities
-
Core cutting: Silencer shear line with 0.02mm accuracy, step-lap joints.
-
Vacuum drying & oil filling: Residual moisture ≤ 0.5% in insulation (measured by Karl Fischer).
-
Pressure leak test: 0.3 bar air pressure for 12 hours – zero drop allowed.
-
Partial discharge (PD) test: ≤ 10pC at 1.1× rated voltage (IEC 60076-3).
Why Nigeria customers choose HENTG POWER
-
Every transformer shipped with individual oil sample test report (breakdown voltage, moisture, dielectric dissipation factor).
-
Customizable for 50Hz grid fluctuations (±10% voltage, ±5% frequency) – internal design margin for +15% voltage.
-
10-year spare parts availability commitment for gaskets, bushings, and cooling fins.

-
Transformador Subestação de Potência Tipo Imerso em Óleo Elevador 125 Kva 12 Kv
Transformador de tipo imerso em óleo 125 KVA 12 KV Transformador de potência de subestação Especificações do produto Atributo Valor Tipo Transformador de distribuição, transformador cheio de óleo Materiais Cobre, alumínio, enrolamento de cobre Frequência 60Hz, 50Hz Material de enrolamento Cobre, ...
-
Transformador Ajustável de Tensão Imerso em Óleo 6.3-10KV 250-630kVA 3 Fases Multi-Enrolamento
Transformador Imerso em Óleo de Tensão Ajustável 6.3-10KV 250-630kVA 3 Fases Multi Enrolamento Atributos do Produto Atributo Valor Frequência 50Hz, 60Hz Número de Bobinas Três Enrolamentos, Multi Enrolamento, Dois Enrolamentos, Enrolamento Único Aplicação Sistema de distribuição Estrutura da Bobina ...
-
Transformador Imerso em Óleo de Média Tensão 315kVA a 630kVA Transformador de Distribuição Trifásico 60Hz
Transformador a óleo MV HV 315kVA a 630kVA Transformador de distribuição trifásico 60Hz Especificações do Produto Atributo Valor Frequência 60Hz Fase Trifásico, Monofásico Aplicação Transformador de Potência Tensão de Saída 415V, 380V, 400V, 110V, 220V, 440V, 480V Tensão de Entrada 11kV, 10,5kV, 6...