New Energy Outdoor Power Distribution Equipment Step Up/Down Electricity Power Substation Advanced Energy Storage
HENTG New Energy Outdoor Power Distribution Equipment Step Up/Down Electricity Power Substation with Advanced Energy Storage Product Characteristics The vacuum circuit breaker or load switch + fuse (combined electrical appliance) technical solution can be used on the high voltage side of Huashi box. ...
33kV oil immersed power transformer
,5000kVA Dyn11 transformer
,ONAN cooling power transformer
The vacuum circuit breaker or load switch + fuse (combined electrical appliance) technical solution can be used on the high voltage side of Huashi box. This configuration ensures safe operation with the following features:
- Automatic power cutoff when any phase fuse is blown, enabling safe fuse replacement before main switch closure
- Mechanical interlocks prevent misoperation
- Real-time status monitoring and remote control capability

| Item | Parameter | No | Item | Parameter |
|---|---|---|---|---|
| Basic Technical Parameters | 2 | Insulation & Thermal Classes | ||
| Type & Model | S11-5000-33/0.69 | Insulation Level | Class A | |
| Rated Capacity | 5000kVA | a | High-Voltage Side | |
| Rated Voltage(HV / LV) | 33kv/0.69kv | Lightning Impulse Withstand(peak) | 200kv | |
| Rated Current(HV / LV) | 87.5A /4183.7 A | Short-Duration Power-Frequency Withstand(r.m.s.) | 85kv | |
| Voltage Ratio | ±2 * 2.5 % | Lightning Impulse Withstand (peak) | ||
| Short-Circuit Impedance | 7% | Short-Duration Power-Frequency Withstand (r.m.s.) | 5kv | |
| Vector Group | Dyn11 | |||
| Rated Frequency | 50Hz | |||
| Cooling Method | ONAN | |||
| Losses, Noise & No-Load Current | 4 | Other Technical Requirements | ||
| No-Load Loss | ≤ 3970W (+15%) | 4 | Overall Dimensions (L * W * H) | 2650 mm * 2900 mm * 2750 mm |
| Load Loss | ≤ 39018W (+15%) | b. | Estimated Total Mass | 10.7t |
| Sound Pressure Level | ≤ 77 dB(A) | |||
| No-Load Current | 0.50% |

- Full-condition simulation pre-commissioning: Over 100 tests completed in-plant to ensure error-free on-site commissioning
- Military-grade protective enclosure: High-strength steel with C5-level corrosion resistance and IP54 protection rating
- Intelligent internal environment: Industrial climate control with air conditioning, fans, heaters, and gas fire protection
- Modular design: Flexible configuration from 500kVA to 10MVA capacity
- Future-ready: Reserved interfaces for easy capacity expansion or upgrades
- Relocatable: Can be moved and reused at new locations after project completion
- Reduced initial investment: Lower civil engineering costs and space requirements
- Lower operating costs: Energy-efficient design with intelligent monitoring for unmanned operation
- Minimized maintenance costs: Modular design enables quick component replacement and predictive maintenance
-
11000KVA Prefabricated Substation for Solar Wind Power 50Hz/60Hz
Power Prefabricated Box Type Substation for Solar Wind Compatible 50/60Hz Three-Phase MV&HV Transformers Renewable Energy Product Characteristics Vacuum circuit breaker or load switch + fuse (combined electrical appliance) technical solution can be used on the high voltage side of Huashi box. The electrical characteristics of the combined electrical structure ensure that when any phase fuse is blown, the load switch will trip to cut off power supply, allowing safe fuse
-
Outdoor Prefabricated Customized 35kv 10kv New Energy Power Combined Box Type Substation Price
Product characteristics Vacuum circuit breaker or load switch + fuse (combined electrical appliancetechnical solution can be used on the high voltage side of Huashi box. The electricalcharacteristics of the combined electrical structure is that when any phase fuse isblown, the load switch will be guaranteed to trip and cut off the power supply, and themain switch can be closed after replacing the fuse. The vacuum circuit breaker or load switch + fuse (combination electrical
-
Three Phase Box Type Substation with 400V-690V Output Voltage and 20kV Rated Voltage for Power Distribution
Three Phase Box Type Substation with 400V-690V Output Voltage and 20kV Rated Voltage for Power Distribution Consulting Process Step 1: We respond to inquiries within 1 hour, recommending suitable transformers based on your requirements. We provide competitive quotations and flexible payment terms. Our professional drawing and technical teams will confirm all drawing details with you within 7 days after payment, including technical specifications, weight, and parts list. Step