Grouding 33kV 2500kVA Zig-Zag Earthing Transformer for Utility Solar PV Plants
HENTG POWER 33kV 2500kVA Zig-Zag Earthing Transformer establishes a reliable neutral point for utility-scale solar PV and BESS collector networks. It provides a controlled zero-sequence current path for effective earth fault detection. Features include customized zero-sequence impedance, neutral CT and relay interfaces, oil-immersed ONAN cooling, and IEC 60076 compliance. Optional tropical, high-altitude and anti-corrosion designs suit harsh environments. EPC engineering support and integrated NGR options available.
33kV zig-zag earthing transformer
,2500kVA oil immersed transformer
,solar PV plant earthing transformer
HENTG POWER 33kV 2500kVA Earthing Transformer for Utility-Scale Solar PV Power Plants
Zig-Zag Grounding Transformer for 33kV Solar Collector Networks
Product Overview
HENTG POWER 33kV Earthing Transformers are specifically engineered to establish a reliable neutral grounding point in medium-voltage solar power collection systems.
In utility-scale photovoltaic power plants, inverter step-up transformers and delta-connected collector networks may not provide an accessible neutral point. Our Zig-Zag Earthing Transformer provides a controlled zero-sequence current path, enabling effective earth fault detection and supporting stable grid-connected operation.
The transformer can be customized according to the solar plant's single-line diagram, grounding philosophy, grid connection requirements and environmental conditions.
Product Highlights
Dedicated Solar PV Grounding Design
Suitable for medium-voltage solar collector networks and renewable energy substations.
Zig-Zag Winding Configuration
Establishes an artificial neutral point without requiring a conventional secondary winding.
Customized Earth Fault Current Rating
Engineered according to project-specific grounding and protection requirements.
Outdoor Operation Capability
Optional tropical climate, high-altitude and anti-corrosion designs.
EPC Engineering Support
Technical selection, drawing approval, protection interface coordination and factory testing.
Technical Design Features
| Technical Item | Design Description |
|---|---|
| Rated System Voltage | 33kV, with other MV voltage classes available upon request |
| Reference Capacity | 2500kVA / 2.5MVA, subject to grounding duty definition |
| Winding Configuration | Zig-Zag (ZN) |
| Neutral Point | Accessible neutral terminal for external grounding equipment |
| Zero-Sequence Impedance | Customized according to earth fault calculations |
| Neutral Fault Current | Designed according to the specified grounding current |
| Fault Current Duration | Project-specific, coordinated with protection clearing time |
| Grounding Method | Direct grounding, NGR or other engineered grounding arrangements |
| Cooling Method | Oil-immersed ONAN |
| Insulation Coordination | Selected according to system voltage, BIL and installation conditions |
| Applicable Standards | IEC 60076 series, including IEC 60076-6 where applicable |
The Zig-Zag winding arrangement provides a low-impedance path for zero-sequence current while presenting relatively high impedance to balanced positive-sequence excitation. This allows the transformer to establish a system neutral without carrying the solar plant's normal generation power.
Winding conductors, insulation systems and mechanical structures are designed to withstand the specified thermal and electromagnetic stresses during earth faults.
Solar Power Plant Grounding Solution
Typical PV collector system grounding arrangement — protection and switching devices omitted for clarity.
HENTG POWER provides a project-specific grounding solution for solar farms using 11kV, 33kV or other medium-voltage collector systems.
Our engineering support includes selecting the grounding transformer, coordinating the neutral grounding resistor, reviewing insulation requirements and supporting the EPC contractor in integrating the equipment into the plant's MV switchgear and protection system.
This solution helps address neutral displacement, earth fault detection and grounding-related overvoltage risks.
Frequently Asked Questions
Q1: Why does a solar power plant need an earthing transformer?
A: When the collector network has no accessible neutral point, an earthing transformer establishes a neutral reference and provides a defined earth fault current path.
Q2: Can one earthing transformer serve an entire 50MW solar power plant?
A: Potentially, depending on the collector bus configuration, sectionalized operation, transformer locations and grounding study. Plant MW capacity alone cannot determine the required quantity.
Q3: Can the transformer operate in African tropical climates?
A: Yes. High ambient temperature, humidity, dust, solar radiation and altitude can be considered during the design stage.
Q4: Can HENTG POWER supply the transformer together with an NGR?
A: An integrated transformer and NGR solution can be evaluated according to the required neutral current, resistance and fault duration.
Q5: What information should an EPC contractor provide for quotation?
A: System voltage, frequency, single-line diagram, grounding method, required fault current, fault duration and environmental conditions.
Q6: Can distributors obtain technical documents for utility tender submissions?
A: Project-specific datasheets, outline drawings, technical compliance documents and available test reports can be provided according to the tender requirements.
Request Custom Grounding Solution for Solar PV Plants
Contact HENTG POWER for a customized solar power plant grounding solution.
Email: info@hentgpower.com
Send InquiryHENTG POWER — Power Transformation · Smarter Distribution
-
HENTG POWER 500kVA 13.8kV/0.4kV Oil-Immersed Transformer with ONAN Cooling for Outdoor Power Distribution
HENTG POWER 500kVA oil-immersed transformer delivers reliable outdoor power distribution with high-efficiency CRGO core, reinforced anti-leakage tank, and specialized design for harsh African environments. Custom voltage ratios and IEC/ANSI standards available.
-
CE Certified 35KV Oil Immersed Power Transformer with 1250KVA 5000KVA High Efficiency and Low Loss
CE Certified Oil-Immersed Power Transformer 35KV Distribution & Power Transformer 1250KVA 5000KVA 6300KVA Our CE Certified Oil-Immersed Power Transformer is designed for efficient and reliable power distribution in industrial, commercial, and utility applications. Featuring advanced oil insulation, ...
-
HENTG POWER 300kVA 3.3kV/0.4kV Oil-Immersed Transformer with Coastal Anti-Corrosion Design for South Africa
300kVA 3.3kV/0.4kV oil-immersed transformer for South Africa's industrial & coastal networks. Features marine-grade anti-corrosion coating, IEC 60076 compliance, low losses, and enhanced leak-proof design for mining, utility & renewable applications.