High Efficiency Oil Immersed Power Distribution Transformer 400kVA 10kV 0.4kV Three Phase ONAN Type for African Rural Electrification HENTG POWER
HENTG POWER หม้อแปลงไฟฟ้าแบบฝังน้ำมัน 400kVA 10kV 0.4kV ประเภทการกระจาย ONAN สามเฟสสำหรับแอปพลิเคชันกริดแอฟริกัน
10kV 0.4kV Power Distribution Transformer
,ONAN Type Power Distribution Transformer
,African Rural Electrification Power Distribution Transformer


The HENTG POWER 400kVA 10kV/0.4kV three-phase oil immersed distribution transformer is a step-down unit designed for primary and secondary distribution networks in utility grids and commercial electrification projects. This ONAN cooled transformer converts medium voltage from 10kV to a low voltage of 400V/230V, making it suitable for industrial loads, commercial complexes, residential communities, and agricultural processing facilities. Manufactured with reference to IEC 60076 guidelines, this oil immersed transformer features a hermetically sealed corrugated tank and copper windings. The unit is built for steady voltage transformation with specified loss characteristics and reduced maintenance needs in outdoor and high temperature environments. Its sealed construction helps resist dust ingress and moisture absorption, supporting long-term operation across various regional conditions.

-
Designed for 10kV Distribution Networks
The primary voltage rating of 10kV corresponds to the standard medium voltage level used in many utility systems. Optional tapping adjustments accommodate line voltage variations of 10.5kV or 11kV without requiring unit replacement.
-
Core and Winding Design for Energy Efficiency
The transformer uses grain-oriented silicon steel laminations and copper windings to achieve specified no-load and load loss performance. This design supports reduced technical losses in the distribution network and contributes to lower operational expense over the equipment service life.
-
Hermetically Sealed Tank for Dust and Moisture Protection

The fully welded corrugated tank eliminates the need for a conventional conservator and breather system. This sealed construction helps prevent ingress of airborne sand dust and humidity factors known to compromise insulation integrity in arid and coastal African regions. The hermetic design protects internal components from external factors such as dust moisture and temperature fluctuations. -
Thermal Performance for Elevated Ambient Temperatures
The ONAN cooling configuration and corrugated fin surface area are engineered to support natural convective heat transfer. For installation locations with sustained ambient temperatures exceeding forty degrees Celsius the design maintains stable operating temperatures through efficient oil circulation and heat dissipation.
-
Comprehensive Protection and Monitoring Features
Standard equipment includes a pressure relief device, dial type oil temperature indicator, Buchholz relay for gas and oil surge detection, and a drain valve with sampling port. These integrated components provide early fault indication and support predictive maintenance planning.
| Parameter | Value and Description |
|---|---|
| Rated Capacity | 400 kVA |
| Type | Outdoor Three Phase Oil Immersed Distribution Transformer |
| Voltage Ratio Primary Secondary | 10 000V 400V with 230V phase to neutral available |
| Vector Group | Dyn11 Common for unbalanced load handling Yyn0 Optional |
| Cooling Method | ONAN Oil Natural Air Natural |
| Frequency | 50 Hz Common 60 Hz Optional upon request |
| Winding Material | High Conductivity Electrolytic Copper |
| Core Material | Grain Oriented Cold Rolled Silicon Steel |
| Tapping Range | Plus minus two times two point five percent five position off circuit tap changer |
| No Load Loss | Less than or equal to four hundred ten watts |
| Load Loss at seventy five degrees Celsius | Less than or equal to four thousand five hundred twenty watts |
| No Load Current | Less than or equal to zero point eight percent of rated current |
| Impedance Voltage | Four point zero percent with plus minus ten percent tolerance |
| Insulation Class | Class A one hundred five degrees Celsius Optional Class B or F for high ambient areas |
| Tank Construction | Corrugated Fins Hermetically Sealed No Conservator No Breather |
| Insulating Oil | IEC 60296 Class I Inhibited Mineral Oil PCB Free |
| Protection Degree | IP23 Weatherproof Terminal Box |
| Applicable Reference Standards | IEC 60076 IEEE C57 dot 12 dot 00 GB 1094 |
Additional Technical Notes
The Dyn11 vector group allows the transformer to handle single phase load imbalances effectively a common requirement in mixed residential commercial and light industrial distribution networks. The off circuit tap changer located on the tank side wall permits voltage ratio adjustment without opening the main tank cover. The corrugated fin design maximizes surface area for natural heat dissipation supporting continuous operation at rated load in elevated ambient temperatures. The core is constructed from high grade grain oriented cold rolled silicon steel laminations for minimal no load loss and reduced audible noise.
Operational Challenges in Dust Prone and High Temperature African Environments
In many African regions distribution transformers face two primary environmental stressors. First pervasive fine sand and laterite dust infiltrates conventional breather systems and abrades gasket sealing surfaces over time. Second sustained high ambient temperatures combined with daily thermal cycling cause oil volume expansion and contraction which can stress bolted joints and seal interfaces leading to slow oil seepage or moisture ingress. These conditions increase maintenance frequency shorten insulation life and elevate the risk of unplanned service interruptions.
HENTG POWER Design Measures for Reliable Field Performance
-
Hermetic Sealing Without Breather Assembly
The 400kVA transformer employs a fully welded corrugated tank that flexes to accommodate oil volume changes due to temperature variation. By eliminating the traditional silica gel breather the unit removes the primary entry pathway for abrasive airborne dust and humid air. The hermetic sealing prevents ingress of moisture and contaminants maintaining the integrity of the insulating oil.
-
Reinforced Gasket and Flange Configuration
Critical sealing interfaces including handhole covers bushing mounting plates and the tap changer flange utilize Nitrile Butadiene Rubber NBR gaskets retained within precision machined grooves. This groove retained design prevents gasket extrusion or creep under thermal and mechanical stress while the multi bolt fastening pattern helps maintain uniform compression even after prolonged exposure to road vibration during transport to remote project sites.
-
Continuous Welding and Leak Testing
The tank body is constructed using continuous welding techniques and undergoes pressure testing before finishing. This all welded structure helps verify the integrity of weld seams and greatly reduces the risk of oil leakage during long term field operation.
-
Protective Exterior Coating System
The tank exterior and all external metalwork receive a multi layer coating comprising an epoxy zinc rich primer and an aliphatic polyurethane topcoat. This system provides resistance to corrosion UV degradation and abrasive sand scouring helping maintain the structural and sealing integrity of weld seams and flanged connections over decades of outdoor exposure.
-
Thermal Performance for Elevated Ambient Temperatures
The ONAN cooling configuration and generous corrugated fin surface area are engineered to support natural convective heat transfer. For installation locations with sustained ambient temperatures exceeding forty degrees Celsius optional upgrades to Class B or Class F insulation systems are available upon request allowing the transformer to manage thermal stress without accelerated cellulose degradation.
-
Q1 Is the 10kV primary rating compatible with 11kV or 10.5kV distribution networks found in various African countries
A Yes The standard transformer is supplied with a five position off circuit tap changer providing a tapping range of plus minus two times two point five percent This allows the unit to be field adjusted for operation on 10kV 10.5kV or 11kV systems For networks operating at 13.8kV or 15kV a dedicated primary winding configuration can be provided upon request during the quotation stage
-
Q2 What is the estimated production and delivery timeline for a container order of 400kVA transformers to a port such as Dar es Salaam or Tema
A For standard specification units with copper windings and Dyn11 vector group the production lead time is typically within thirty to thirty five days from order confirmation to port of loading Ocean freight transit time to major African ports is additional and varies by shipping line schedule We provide complete export documentation support including Certificate of Origin and any required destination inspection documentation
-
Q3 What are the recommended periodic maintenance activities for this hermetically sealed transformer operating in a dusty remote area
A This transformer is designed as a low maintenance sealed unit There is no silica gel breather to service and no requirement for routine oil top up under normal operating conditions Recommended annual inspection includes visual assessment of the external paint coating verification of oil level via the sight gauge and a functional check of the pressure relief device Periodic oil sampling for Dissolved Gas Analysis is advised every two to three years to monitor internal condition non intrusively
-
Q4 How does the transformer perform in sustained high ambient temperatures above forty degrees Celsius
A The ONAN cooling system and corrugated fin design maximize natural heat dissipation surface area For regions with sustained high ambient temperatures or high solar radiation we offer an upgraded thermal class option Class B or F insulation with sixty five Kelvin temperature rise This allows the transformer to operate continuously at rated load in elevated temperatures without accelerated aging of the insulation paper
-
Q5 Can this transformer be supplied with aluminum windings as a cost reduction measure for budget sensitive electrification tenders
A Yes Aluminum winding construction is available as an alternative to the standard copper winding configuration This option may offer initial purchase savings though it typically results in slightly larger overall dimensions and marginally higher load loss values Our technical team can provide comparative performance data to support informed procurement decisions
-
Q6 Is technical support available for site acceptance testing and commissioning at EPC project locations
A HENTG POWER offers a range of field support services These can include provision of detailed installation and testing manuals remote commissioning guidance via video conference and upon separate agreement dispatch of a factory trained technician to the project site for supervision of installation and pre energization checks
Contact HENTG POWER today to request a detailed quotation and technical datasheet for the 400kVA 10kV 0.4kV oil immersed transformer including shipping options to African ports

-
250kVA 10kV to 0.4kV Oil-Immersed Distribution Power Transformer for Rural Electrification
Factory Price S11 250kVA 10kV to 0.4kV Distribution Power Transformer for Rural Electrification Product Overview The Factory Price S11-250kVA 10kV to 0.4kV Distribution Power Transformer is a high-performance, three-phase oil-immersed unit specifically engineered for rural electrification and agricultural power grids . As an industry-standard step-down transformer, the S11 series balances cost-efficiency with exceptional reliability. Whether for remote village power supply,
-
IEC60076 High Efficiency 630kVA 10/0.4 Copper Winding Oil-Immersed Transformer With oil Conservator For Residential Electrical Applications Manufacturer
หม้อแปลงน้ำมัน IEC60076 630kVA พร้อมขดลวดทองแดงและการระบายความร้อน ONAN การออกแบบป้องกันการรั่วไหลประสิทธิภาพสูงสำหรับสภาพแวดล้อมที่รุนแรง ตัวเลือกที่ปรับแต่งได้ รับประกัน 1 ปี พลังงานที่เชื่อถือได้สำหรับการใช้งานในที่พักอาศัยและเชิงพาณิชย์
-
Reliable 315kva transformer price Oil Immersed Distribution Transformer with Dust Resistant Sealing for African Conditions
หม้อแปลงแช่น้ำมันขนาด 315kVA พร้อมซีลกันฝุ่นสำหรับสภาวะในแอฟริกา นำเสนอการสูญเสียต่ำ (480W ขณะไม่โหลด) ได้รับการรับรอง IEC/CE และการป้องกันการกัดกร่อนที่ได้รับการปรับปรุงสำหรับสภาพแวดล้อมที่รุนแรง